220kV变电所设计+主变容量+短路计算+设备选择校验 第8页
基准容量:Sb = 100MVA
冲击系数:kch = 1.8
如图3-1所示:
220kV侧:电源的标幺值:E1 = 1
归算至本所220kV母线侧阻抗为X1=0.016(Sb =100MVA)
110kV侧:电源的标幺值:E2 = 1
归算至本所110kV母线侧阻抗为X1=0.32(Sb =100MVA)
X5 = XT1=0.11875 X6 = XT2=-0.00625 X7 = XT3=0.06792
X8 = X5,X9 = X6,X10 = X7
可知X12 = X5 / 2=0.11875/2=0.059375
X13 = X6 / 2=-0.00625=-0.003125
X14 = X7 / 2=0.06792=0.03396
图3-2 等效变换后的等值电路图
D1点短路时的情况:
等效电阻:X21 = X2 + X13 + X12
=0.32-0.003125+0.059375
=0.37625
短路电流的周期分量的标幺值为:
id1 = E2 / X21 + E1 / X1
=1/0.37625+1/0.016
=65.1578
D1点的电流基准值为:ib=100/( )kA=0.251kA
短路电流的周期分量的有名值为:id1 0.251kA=16.356kA
冲击电流的有名值为:ich = kch id1 0.251=41.6356kA
短路电流的全电流有效值为:iq = id1 0.251kA=24.697kA
短路容量:St=id1 Sb=6515.78MVA
D2点短路时的情况:
等效电阻:X22 = X1 + X12 + X13
=0.016+0.059375-0.003125
=0.07225
短路电流的周期分量的标幺值为:
id2 = E1 / X22 + E2 / X2=1/0.07225+1/0.32=16.9658
D2点的电流基准值为:ib=100/( )kA=0.502kA
短路电流的周期分量的有名值为:id2 0.502kA=8.5176kA
冲击电流的有名值为:ich = kch id2 0.502=21.6822kA
短路电流的全电流有效值为:iq = id2 0.502kA=12.8613kA
短路容量:St=id2 Sb=1696.58MVA
D3点短路时的情况:
等效电阻:X23 = X14 + (X2 + X13) (X1 + X12) / (X2 + X13 + X1 + X12)
=0.03396+(0.32-0.003125)(0.016+0.059375)/(0.32-0.003125+0.016+0.059375)
=0.09485
E3 = (E1 × (X2 + X13) + E2 × (X1 + X12)) / (X2 + X13 + X1 + X12)
=(1 (X2 + X13) + 1 (X1 + X12)) / (X2 + X13 + X1 + X12)=1
短路电流的周期分量的标幺值为:
id3 = E3 / X23=1/0.09485=10.5428
D3点的电流基准值为:ib=100/( )kA=5.4986kA
短路电流的周期分量的有名值为:id3 5.4986kA=57.97kA
冲击电流的有名值为:ich = kch id3 5.4986=147.5684kA
短路电流的全电流有效值为:iq = id3 5.4986kA=87.533kA
短路容量:优'文-论"文.网http://www.chuibin.com St=id3 Sb=1054.28MVA
(二)计及负荷的影响
计算等值网络中的各个元件的标幺值,在这里先将全部负荷计入,以额定标幺电抗为0.35,电势为0.8的电源表示。
基准容量:Sb = 100MVA
系统的冲击系数:kch = 1.8
负荷的冲击系数:kp=1
如图3-6所示:
220kV侧:
电源的标幺值:E1 = 1
归算至本所220kV母线侧阻抗为X1=0.016(Sb =100MVA)
110kV侧:
电源的标幺值:E2 = 1
归算至本所110kV母线侧阻抗为X1=0.32(Sb =100MVA)
负荷的容量为冶炼厂的负荷容量,即S110=80MVA
X3 = 0.35 Sb / S110=0.35 100/80=0.4375
10kV侧:
负荷容量按最大负荷容量S10=40MVA
X4=0.35 Sb/S10=0.35 100/40=0.875
上一页 [1] [2] [3] [4] [5] [6] [7] [8]
220kV变电所设计+主变容量+短路计算+设备选择校验 第8页下载如图片无法显示或论文不完整,请联系qq752018766